Power Products X900UC2_208 Generator Set, equipped with an MTU engine and a LEROY SOMER alternator.
Direct access to sections
GENERAL FEATURES
General characteristics
Description
Power table
Engine type 16V2000G45E
Performance class G3
Frequency (Hz) 60
Reference voltage (V) 208/120
Max power ESP (kVA) 1125
Max power ESP (kWe) 900
Max power PRP (kVA) 1022.70
Max power PRP (kWe) 818.20
Current (A) 3123
Standard cabinet BORNIER
Optional cabinet M80
Optional cabinet TELYS
Optional cabinet APM802
Electronic regulation
Mechanically welded chassis with anti-vibration suspensions
Radiator with mechanical fan (see performance table for temperature)
Exhaust compensator(s) with flanges
Starter and charging alternator 24V
Delivered with oil and coolant -30°C
User manual and commissioning guide
Voltages ESP PRP Amperes
backup
kWe kVA kWe kVA
208/120 900 1125 818 1023 3123
ENGINE FEATURES
General data
Exhaust
Fuel
Oil
Thermal balance
Intake air
Cooling system
Emissions
Engine brand MTU
Engine ref. 16V2000G45E
Aspiration type Turbo
Intake air cooling Air/Air DC
Number of cylinders 16
Cylinder arrangement V
Displacement (L) 31.86
Bore (mm) 130
Stroke (mm) 150
Compression ratio 16
Speed (RPM) 1800
Piston speed (m/s) 9
ESP power (kW) 1010
Regulation class (%) +/- 0.5%
BMEP (bar) 19.10
Regulation type Electronic
Exhaust gas temperature @ ESP 60Hz (°C) 520
Exhaust gas flow @ ESP 60Hz (L/s) 3200
Exhaust back pressure (mm H2O) 500
Consumption 110% (L/h) 240
Consumption 100% load (L/h) 219
Consumption 75% load (L/h) 168
Consumption 50% load (L/h) 114
Max fuel pump flow (L/h) 480
Oil capacity (L) 102
Min oil pressure (bar) 4.70
Max oil pressure (bar) 7.50
Oil consumption 100% load (L/h) 2.19
Oil sump capacity (L) 92
Heat rejected in exhaust (kW) 700
Radiated heat (kW) 45
Heat rejected in water (kW) 350
Max intake back pressure (mm H2O) 150
Combustion air flow (L/s) 1350
Engine and radiator capacity (L) 205
Max water temperature (C°) 102
Water outlet temperature (C°) 95
Fan power (kW) 43
Fan air flow Dp=0 (m3/s) 21.55
Available back pressure on air (mm H2O) 20
Refrigerant type Glycol-Ethylene
HT thermostat (°C) 75-88
Emission PM (g/kW.h) 0.03
Emission CO (g/kW.h) 0.46
Emission HC (g/kW.h) 0.13
ALTERNATOR FEATURES
General data
Other data
Commercial brand of the alternator LEROY SOMER
Alternator ref. LSA 49.1 L11
Number of phases Three-phase
Power factor (cos Phi) 0.80
Altitude (m) 0 to 1000
Overspeed (rpm) 2250
Number of poles 4
Insulation class H
Temperature class (H/125°) continuous 40°C H / 125°K
AVR type R450
Total harmonic distortion at no load DHT (%)
Waveform: NEMA = TIF
Waveform: IEC = FHT
Number of bearings 1
Direct coupling
Voltage regulation at steady state (+/- %) 0.50
Continuous rated power 40°C (kVA) 1040
Backup power 27°C (kVA) 1145
Efficiency at 100% load (%) 94.90
Air flow (m3/s) 1.40
Short circuit ratio (Kcc) 0.2760
Unsaturated synchronous longitudinal reactance (Xd) (%) 399
Unsaturated synchronous transverse reactance (Xq) (%) 203
Transient time constant at no load (T'do) (ms) 2111
Saturated transient longitudinal reactance (X'd) (%) 18.90
Transient time constant in short circuit (T'd) (ms) 100
Saturated subtransient longitudinal reactance (X''d) (%) 15.10
Subtransient time constant (T''d) (ms) 10
Subtransient time constant (T''q) (ms) 10
Saturated subtransient transverse reactance (X''q) (%) 16.40
Unsaturated homopolar reactance (Xo) (%) 0.20
Saturated inverse reactance (X2) (%) 15.82
Armature resistance (Ra) (%) 0.0120
Armature leakage reactance (Xa) (%) 0.94
Armature time constant (Ta) (ms) 15
No-load excitation current (io) (A) 0.59
Load excitation current (ic) (A) 2.82
Load excitation voltage (uc) (V) 33.20
Response time (Delta U = 20% transient) (ms) 500
Starting (Delta U = 20% permanent or 50% transient) (kVA) 1952.58
Transient Delta U 4/4 load-Cos Phi 0.8 AR (%) 13
No-load loss (W) 14638.22
Heat dissipation (W) 44604.28
DIMENSIONS
Dimensions compact version
Dimensions soundproof version
Length (mm) 4320
Width (mm) 1971
Height (mm) 2250
Net weight (kg) 6323
Tank capacity (L) 0
Type of soundproofing M427
Length (mm) 6400
Width (mm) 2170
Height (mm) 2721
Net weight (kg) 9207
Tank capacity (L) 930
Sound pressure level @1m dB(A) 95
Sound pressure level @7m dB(A) 86
CABINET
BORNIER
M80, information reporting
TELYS, ergonomic and user-friendly
APM802 dedicated to energy management
The cabinet serves as a simple terminal for connecting an electrical cabinet.
It offers the following features:
Emergency stop button, customer connection terminal, CE compliance.
The M80 cabinet has a dual functionality. It serves as a simple terminal for connecting an electrical cabinet and as a direct reading dashboard whose gauges allow monitoring of the basic parameters of your generator set.
It offers the following features:
Engine parameters: Tachometry, Hour meter, Water temperature indicator, Oil pressure indicator, Emergency stop button, Customer connection terminal, CE compliance.
Extremely versatile, the TELYS cabinet is complete yet remains very accessible thanks to in-depth work on optimizing ergonomics and user-friendliness. With a large display screen, buttons, and a scrolling knob, it opts for simplicity and emphasizes communication.
It offers the following features:
Electrical measurements: Voltmeter, Ammeter, Frequency meter.
Engine parameters: Hour meter, Oil pressure, Water temperature, Fuel level, Engine speed, Battery voltage.
Alarms and faults: Oil pressure, Water temperature, No start, Overspeed, Min/max alternator, Min/max battery voltage, Emergency stop, Fuel level.
Ergonomics: Navigation knob between different menus.
Communication: Remote control and monitoring software, USB connections, PC connection.
For more information about the product and its options, please refer to the commercial documentation.
The new APM802 control cabinet is dedicated to the operation and monitoring of energy plants for the hospital, data center, banking, oil and gas, industrial, IPP, rental, and mining markets.
This cabinet is standard on all generator sets from 275 kVA intended for coupling functions. For the rest of our range, it is optional.
The human-machine interaction, designed in collaboration with a company specialized in interaction design, facilitates operation with a 100% touch screen. The pre-configured system for energy plant applications features a unique customization function compliant with the international standard IEC 61131-3. New communication functions (automation and regulation) enhance the high availability of the installation's equipment.
Highlights:
Dedicated to energy plant management.
Ergonomics specially designed
High availability of equipment
Guaranteed modularity and sustainability
Facilitated installation extension
For more information, please refer to the commercial documentation.