Power Products X3100 Generator Set, equipped with an MTU engine and a LEROY SOMER alternator.
Direct access to sections
GENERAL FEATURES
General characteristics
Description
Power table
Engine type 20V4000G63F
Performance class G3
Frequency (Hz) 50
Reference voltage (V) 400/230
Max ESP power (kVA) 3100
Max ESP power (kWe) 2480
Max PRP power (kVA) 2818.20
Max PRP power (kWe) 2254.50
Current (A) 4475
Standard cabinet TERMINAL
Optional cabinet M80
Optional cabinet TELYS
Optional cabinet APM802
Electronic regulation
Mechanically welded chassis with anti-vibration suspensions
Air cooler for temperature range 47/50°C with electric fan
Exhaust compensator(s) with flanges
Starter and charging alternator 24V
Delivered with oil
User manual and commissioning guide
Voltages ESP PRP Amperes
backup
kWe kVA kWe kVA
415/240 2480 3100 2255 2818 4313
400/230 2480 3100 2255 2818 4475
380/220 2480 3100 2255 2818 4710
ENGINE FEATURES
General data
Exhaust
Fuel
Oil
Thermal balance
Intake air
Cooling system
Emissions
Engine brand MTU
Engine ref. 20V4000G63F
Aspiration type Turbo
Intake air cooling Air/Water DC
Number of cylinders 20
Cylinder arrangement V
Displacement (L) 95.33
Bore (mm) 170
Stroke (mm) 210
Compression ratio 16.4
Speed (RPM) 1500
Piston speed (m/s) 10.50
ESP power (kW) 2662
Regulation class (%) +/- 0.5%
BMEP (bar) 20.31
Regulation type Electronic
Exhaust gas temperature @ ESP 50Hz (°C) 560
Exhaust gas flow @ ESP 50Hz (L/s) 7100
Exhaust back pressure (mm H2O) 500
Consumption at 110% load (L/h) 600
Consumption at 100% load (L/h) 535
Consumption at 75% load (L/h) 407
Consumption at 50% load (L/h) 284
Max fuel pump flow (L/h) 1620
Oil capacity (L) 390
Min oil pressure (bar) 4.90
Max oil pressure (bar) 7.70
Oil consumption at 100% load (L/h) 1.63
Oil sump capacity (L) 340
Heat rejected in exhaust (kW) 1598
Radiated heat (kW) 105
Heat rejected in water (kW) 890
Max intake back pressure (mm H2O) 150
Combustion air flow (L/s) 2700
Engine and radiator capacity (L) 815
Max water temperature (°C) 104
Water outlet temperature (°C) 100
Coolant type Glycol-Ethylene
HT thermostat (°C) 79/92
Emission PM (g/kW.h) 0.19
Emission CO (g/kW.h) 1.13
Emission HC (g/kW.h) 0.57
ALTERNATOR FEATURES
General data
Other data
Brand of alternator LEROY SOMER
Alternator ref. LSA 53.1M80
Number of phases Three-phase
Power factor (cos Phi) 0.80
Altitude (m) 0 to 1000
Overspeed (rpm) 2250
Number of poles 4
Insulation class H
Temperature class (H/125°) continuous 40°C H / 125°K
AVR type R449
Total harmonic distortion at no load THD (%)
Waveform: NEMA = TIF
Waveform: IEC = FHT
Number of bearings 1
Direct coupling
Voltage regulation at steady state (+/- %) 0.50
Continuous rated power at 40°C (kVA) 3000
Backup power at 27°C (kVA) 3300
Efficiency at 100% load (%) 96.30
Air flow (m3/s) 2.80
Short circuit ratio (Kcc) 0.35
Unsaturated synchronous longitudinal reactance (Xd) (%) 305
Unsaturated synchronous transverse reactance (Xq) (%) 183
Transient no-load time constant (T'do) (ms) 3060
Saturated transient longitudinal reactance (X'd) (%) 26.70
Transient short circuit time constant (T'd) (ms) 315
Saturated subtransient longitudinal reactance (X''d) (%) 14.50
Subtransient time constant (T''d) (ms) 26
Subtransient time constant (T''q) (ms) 23
Saturated subtransient transverse reactance (X''q) (%) 18.20
Unsaturated homopolar reactance (Xo) (%) 3.40
Saturated inverse reactance (X2) (%) 16.40
Armature reactance (Ra) (%) 0.90
Armature leakage reactance (Xa) (%) 8.60
Armature time constant (Ta) (ms) 68
No-load excitation current (io) (A) 1.30
Load excitation current (ic) (A) 5.10
Load excitation voltage (uc) (V) 61
Response time (Delta U = 20% transient) (ms) 800
Starting (Delta U = 20% permanent or 50% transient) (kVA) 6000
Transient Delta U 4/4 load-Cos Phi 0.8 AR (%) 12.60
No-load loss (W) 27400
Heat dissipation (W) 92200
DIMENSIONS
Dimensions compact version
Dimensions soundproof version
Length (mm) 5730
Width (mm) 2250
Height (mm) 2454
Net weight (kg) 18365
Tank capacity (L) 0
Length (mm) 0
Width (mm) 0
Height (mm) 0
Net weight (kg) 0
Tank capacity (L) 0
Sound pressure level @1m dB(A) 0
Guaranteed acoustic power level (Lwa) 0
CABINET
TERMINAL
M80, information reporting
TELYS, ergonomic and user-friendly
APM802 dedicated to energy management
The cabinet serves as a simple terminal for connecting an electrical cabinet.
It offers the following features:
Emergency stop button, customer connection terminal, CE compliance.
The M80 cabinet has a dual functionality. It serves as a simple terminal for connecting an electrical cabinet and as a direct reading dashboard with dials that allow monitoring of the basic parameters of your generator set.
It offers the following features:
Engine parameters: Tachymetry, Hour meter, Water temperature indicator, Oil pressure indicator, Emergency stop button, Customer connection terminal, CE compliance.
Extremely versatile, the TELYS cabinet is comprehensive yet remains very accessible due to in-depth work on optimizing ergonomics and user-friendliness. With a large display screen, buttons, and a scrolling knob, it opts for simplicity and emphasizes communication.
It offers the following features:
Electrical measurements: Voltmeter, Ammeter, Frequency meter.
Engine parameters: Hour meter, Oil pressure, Water temperature, Fuel level, Engine speed, Battery voltage.
Alarms and faults: Oil pressure, Water temperature, No start, Overspeed, Min/max alternator, Min/max battery voltage, Emergency stop, Fuel level.
Ergonomics: Navigation knob between different menus.
Communication: Remote control and monitoring software, USB connections, PC connection.
For more information about the product and its options, please refer to the commercial documentation.
The new APM802 control cabinet is dedicated to the operation and monitoring of energy plants for the hospital, data center, banking, oil and gas, industrial, IPP, rental, and mining markets.
This cabinet is standard on all generator sets from 275 kVA intended for coupling functions. For the rest of our range, it is optional.
The human-machine interaction, designed in collaboration with a company specializing in interaction design, facilitates operation with a 100% touch screen. The pre-configured system for energy plant applications features a unique customization function compliant with the international standard IEC 61131-3. New communication functions (automation and regulation) enhance the high availability of the installation's equipment.
Highlights:
Dedicated to energy plant management.
Ergonomics specially designed
High availability of equipment
Guaranteed modularity and sustainability
Facilitated installation extension
For more information, please refer to the commercial documentation.