Power Products D300U Generator Set, equipped with a DOOSAN engine and an alternator.
Direct access to sections
GENERAL FEATURES
General characteristics
Description
Power table
Engine type P126TI-II
Performance class G3
Frequency (Hz) 60
Reference voltage (V) 480/277
Max ESP power (kVA) 375
Max ESP power (kWe) 300
Max PRP power (kVA) 340.90
Max PRP power (kWe) 272.70
Current (A) 451
Standard enclosure APM303
Optional enclosure TELYS
Optional enclosure APM802
Optional enclosure TERMINAL
Electronic regulation
Mechanically welded chassis with anti-vibration suspensions
Power circuit breaker
Radiator for temperature range 48/50°C max with mechanical fan
Fan protection grille and rotating parts (CE option)
Silencer attenuation 9dB(A) supplied separately
Charged battery(ies) with electrolyte
Starter and charging alternator 24V
Delivered with oil and coolant -30°C
User and commissioning manual
Voltages ESP PRP Amperes
backup
kWe kVA kWe kVA
480/277 300 375 273 341 451
208/120 300 375 273 341 1041
ENGINE FEATURES
General data
Exhaust
Fuel
Oil
Thermal balance
Intake air
Cooling system
Emissions
Engine brand DOOSAN
Engine ref. P126TI-II
Aspiration type Turbo
Cooling air intake Air/Air DC
Number of cylinders 6
Cylinder arrangement L
Displacement (L) 11.05
Bore (mm) 123
Stroke (mm) 155
Compression ratio 17:1
Speed (RPM) 1800
Piston speed (m/s) 9.30
ESP power (kW) 342
Regulation class (%) +/- 0.5%
BMEP (bar) 18.50
Regulation type Electronic
Exhaust gas temperature @ ESP 60Hz (°C) 580
Exhaust gas flow @ ESP 60Hz (L/s) 1070
Exhaust back pressure (mm H2O) 600
Consumption 110% (L/h) 89.50
Consumption 100% load (L/h) 73.80
Consumption 75% load (L/h) 56
Consumption 50% load (L/h) 37
Max fuel pump flow (L/h) 320
Oil capacity (L) 25
Min oil pressure (bar) 0.50
Max oil pressure (bar) 10
Oil consumption 100% load (L/h) 0.0740
Oil sump capacity (L) 23
Heat rejected in exhaust (kW) 288
Radiated heat (kW) 41.10
Heat rejected in water (kW) 197.0
Max intake back pressure (mm H2O) 635
Combustion air flow (L/s) 470
Engine and radiator capacity (L) 50.50
Max water temperature (C°) 103
Fan power (kW) 15
Fan air flow Dp=0 (m3/s) 7.30
Available back pressure on air (mm H2O) 76
Refrigerant type Glycol-Ethylene
HT thermostat (°C) 71 - 85
Emission PM (g/kW.h) 0.158
Emission CO (g/kW.h) 0.114
Emission HC (g/kW.h) 0.373
ALTERNATOR FEATURES
General data
Other data
Alternator ref. AT01720T
Number of phases Three-phase
Power factor (cos Phi) 0.80
Altitude (m) 0 to 1000
Overspeed (rpm) 2250
Number of poles 4
Insulation class H
Temperature class (H/125°) continuous 40°C H / 125°K
AVR type DSR
Total harmonic distortion at no load THD (%) 2.6
Waveform: NEMA = TIF
Waveform: IEC = FHT
Number of bearings 1
Direct coupling
Voltage regulation at steady state (+/- %) 1
Continuous rated power 40°C (kVA) 360
Backup power 27°C (kVA) 396
Efficiency at 100% load (%) 94.70
Air flow (m3/s) 0.65
Short circuit ratio (Kcc) 0.43
Unsaturated synchronous longitudinal resistance (Xd) (%) 215.30
Unsaturated synchronous transverse resistance (Xq) (%) 124.20
Transient time constant at no load (T'do) (ms) 1400
Saturated transient longitudinal resistance (X'd) (%) 13.10
Transient time constant in short circuit (T'd) (ms) 91
Saturated subtransient longitudinal resistance (X''d) (%) 7
Subtransient time constant (T''d) (ms) 12
Subtransient time constant (T''q) (ms) 20
Saturated subtransient transverse resistance (X''q) (%) 17.90
Unsaturated homopolar resistance (Xo) (%) 2.38
Saturated inverse resistance (X2) (%) 13.80
Armature resistance (Ra) (%) 0.0170
Armature leakage resistance (Xa) (%) 3.80
Armature time constant (Ta) (ms) 16
No-load excitation current (io) (A) 0.70
Load excitation current (ic) (A) 3.80
Load excitation voltage (uc) (V) 59.70
Response time (Delta U = 20% transient) (ms) 200
Starting (Delta U = 20% permanent or 50% transient) (kVA) 276
Transient Delta U 4/4 load-Cos Phi 0.8 AR (%) 14
No-load loss (W) 4228
Heat dissipation (W) 16118
DIMENSIONS
Dimensions compact version
Dimensions soundproof version
Length (mm) 3160
Width (mm) 1340
Height (mm) 1592
Net weight (kg) 2440
Tank capacity (L) 470
Soundproofing type M228
Length (mm) 4475
Width (mm) 1410
Height (mm) 2430
Net weight (kg) 3540
Tank capacity (L) 470
Sound pressure level @1m dB(A) 85
Sound pressure level @7m dB(A) 75
ENCLOSURE
APM303, essentials made simple
TELYS, ergonomic and user-friendly
APM802 dedicated to energy management
TERMINAL
The APM303 is a versatile enclosure allowing operation in manual or automatic mode. It offers the following features:
Measurements:
Single and composite voltage, fuel level.
(Option: active power currents, apparent powers, power factors, kW/h energy meter, oil pressure, coolant temperature)
Supervision:
Modbus RTU communication over RS485
Reports:
(Option: 2 configurable reports)
Protections:
Overspeed, minimum and maximum voltage, minimum and maximum frequency, oil pressure, coolant temperature (maximum active power P)
Traceability:
Stack of 12 recorded events
For more information, please refer to the APM303 technical sheet.
Extremely versatile, the TELYS enclosure is complete yet remains very accessible thanks to in-depth work on optimizing ergonomics and user-friendliness. With a large display screen, buttons, and a scrolling knob, it opts for simplicity and emphasizes communication.
It offers the following features:
Electrical measurements: Voltmeter, Ammeter, Frequency meter.
Engine parameters: Hour meter, Oil pressure, Water temperature, Fuel level, Engine speed, Battery voltage.
Alarms and faults: Oil pressure, Water temperature, No start, Overspeed, Min/max alternator, Min/max battery voltage, Emergency stop, Fuel level.
Ergonomics: Navigation knob between different menus.
Communication: Remote control and operation software, USB connections, PC connection.
For more information on the product and its options, please refer to the commercial documentation.
The new APM802 control panel is dedicated to the operation and monitoring of energy plants for the hospital, data center, banking, oil and gas, industrial, IPP, rental, and mining markets.
This panel is standard on all generator sets from 275 kVA intended for coupling functions. For the rest of our range, it is optional.
The human-machine interaction, designed in collaboration with a company specializing in interaction design, facilitates operation with a large 100% touch screen. The pre-configured system for energy plant applications features a unique customization function compliant with the international standard IEC 61131-3. New communication functions (automation and regulation) enhance the high availability of the installation's equipment.
Highlights:
Dedicated to energy plant management.
Ergonomics specially designed
High availability of equipment
Guaranteed modularity and sustainability
Facilitated installation extension
For more information, please refer to the commercial documentation.
The terminal serves as a simple terminal block for connecting an electrical cabinet.
It offers the following features:
Emergency stop button, customer connection terminal block, CE compliance.